TM 10-3930-641-34-1
(Sheet 4 of 4)
LOCATION/ITEM
ACTION
REMARKS
If voltage does not exceed the preceding
If the voltmeter reads within 10% of the output
stamped on nameplate, the unit is good. If it is
but do not exceed 5000 rpm. Adjust carbon
not good proceed to step 5.
pile to obtain maximum current output.
5. Output 5% or below
Recheck the field coil
If the coil checks good replace the regulator.
See page 3-176
6. Output between 5% and the
Recheck the field coil, stator and diodes.
Repair as required and retest.
recommended 10%
End
3-186