TM 10-3930-675-20-1
0042 00-8
TOPHANDLER SLEWING TROUBLESHOOTING - CONTINUED
0042 00
Table 6. Error Code 259 - Tophandler Counterclockwise Slewing, Component Failure
Troubleshooting Procedures - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Error Code 259 - Tophandler Counterclockwise
Slewing, Component Failure - Continued
4. Enter DIAG ATTACH-
MENT 12 (16) menu and
check current of SLEW CCW
OUTPUT. Current should be
present
with
joystick
activated
to
slew
counterclockwise.
a. If current is not present,
replace ECU (791) (WP 0076
00).
b. If current is present, notify
SRA.