TM 10-3930-675-20-10012 00-8ELECTRONIC CONTROL UNIT (ECU) INPUT VOLTAGE TROUBLESHOOTING - CONTINUED0012 00NOTETophandler ECU (791) has detected a 10V reference voltage out of range (9.3-10.4V).Table 6. Error Code 203 - 10V Reference Voltage for Tophandler ECU (791) Failure Troubleshooting Procedures.MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONError Code 203 - 10V Reference Voltage forTophandler ECU (791) Failure1. Ensure that emergency stopswitch is not activated.Release emergency stop switchas required (TM 10-3930-675-10).2. Remove tophandler junctionbox cover and ensure thatcircuit breaker 51-F41 is nottripped.Reset circuit breaker as required(WP 0076 000).3. Disconnect tophandler anglesensor at connector X180 pins10 and 12.4. Enter the “DIAG Attachment1 (16)” menu and checkvoltage of 10V REF OUT.Voltage should be 9.3-10.4V.If voltage is not as specified,notify SRA.5. Check wires to tophandlerangle sensor.Replace sensor if wires aredamaged (WP 0100 00).