TM 10-3930-675-20-10047 00-8TOPHANDLER TWISTLOCKS AND FORKLIFT SENSOR TROUBLESHOOTING - CONTINUED0047 00Table 5. Error Code 246 - Tophandler Twistlock Unlocking Circuit Failure Troubleshooting Procedures.MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONError Code 246 - Tophandler TwistlockUnlocking Circuit Failure1. Check wires and cables fromtophandler control valve toboom for obvious damage.Repair or replace damaged wires(WP 0111 00).2. Disconnect electricalconnector 6039 fromtophandler twistlockunlocking solenoid. Placeignition switch to ONposition and perform voltagecheck.If 20-25V is present at connector6039, replace twistlockunlocking solenoid (WP 016900).3. Disconnect connector X189from tophandler junction boxat end of boom. Place ignitionswitch to ON position andperform voltage checkbetween connector X189 pinJ and pin K.a. If 20-25V is present, checkcontinuity between con-nector X189 pin J andconnector 6039 pin 1 andbetween connector X189pin K and connector 6039pin 2. Check continuitybetween connector 6039pin 1 and pin 2 and tochassis. Check continuitybetween connector X189pin K and ECU (791)connector 2 pin 8.a. If continuity is not present,repair or replace connectors(WP 0111 00). b. If wiring harness requiresreplacement, notify DSMaintenance.b. If voltage is not present,enter “DIAG ATTACH-MENT 6 (16)” menu andcheck voltage ofUNLOCKED OUTPUT.Voltage should be presentwith joystick lock/unlockand override switch 1005activated (press switchtwice for lock and unlock).a. If voltage is not present,replace ECU (791) (WP 007600).b. If voltage is present, notifySRA.DIAG TOP LIFT 6(16)TW-LOCK OUTPUT INPUTUNLOCKED 0.00V 0MaLOCKED 0.00V0mA