TM 10-3930-675-24-1
TROUBLESHOOTING PROCEDURES (NON-ERROR CODE) - CONTINUED
0007 00
Table 2. Electrical Troubleshooting Procedures (Non-Error Code) - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
20.A/C System Not Cooling Properly - Continued.
c. Replace damaged or faulty
switch (WP 0073 00).
6. Check voltage (24V) at X17 a. If no voltage (24V) is found at
X17 pin 8, check continuity of
pin 8 while operating the A/C
wires A327, 327, 328, and
system to maximum cool.
b. If no voltage (24V) is found at
X17 pin 8 and all wires are
functioning properly, remove
unplug the pressure switch.
Check continuity of the
pressure switch between wires
RD/WH and BK/WH (X810
pins 3 and 4).
c. If no continuity is found at
pressure switch, perform A/C
system maintenance (WP
0265 00) to check the
refrigerant charge of the
system.
7. Check the wire connector at a. If no voltage (24V) is found,
the connector and check
voltage (24V) while operating b. If voltage (24V) is found,
the A/C system to maximum
cool.
compressor clutch to ground.
Ohms.
c. If resistance of compressor
clutch is not as specified,
00).
8. Check circuit breaker F1 for a. Reset circuit breaker as
trip. Unplug X810 and check
required.
voltage (24V) at X810 pins 1 b. If no voltage (24V) is found at
and 2 while operating the A/C
system.
of wires A95A and 322 (WP
0007 00-51