TM 55-8145-201-14
4-6. INSTALLATION INSTRUCTIONS- cont.
(8) Connect five-foot power cable (10) to generator set (9) as follows:
(a) Connect black wire to terminal L3 on generator set (9).
(b) Connect red wire to terminal L2 on generator set (9).
(c) Connect white wire to terminal L1 on generator set (9).
(d) Connect green wire to terminal L0 on generator set (9).
(9) Install cover on generator set terminal box (TM 5-6115-585-12/34).
(10) Connect five-foot power cable (10) to refrigeration unit power cable (11).
(11) Connect interior light cable (12) to 110 Vac receptacle on generator set (TM 5-6115-585-12/34).
CAUTION
To prevent damage to refrigeration unit, stop operation immediately if fan motor runs
backwards.
(12) Service, start, and operate generator set (TM 5-6115-585-12/34).
(13) Service, start, and operate refrigeration unit (TM 9-4110-252-14).
(14) Check rotation of fan motor on refrigeration unit (TM 9-4110-252-14). If motor runs backwards,
shutdown refrigeration unit (TM 9-4110-252-14) and generator set (TM 5-6115-85-12/34), then change
five-foot power cable wiring as follows:
(a) Remove cover from generator set terminal box (TM 5-6115-585-1234).
(b) Disconnect black wire and red wire from generator set (9).
(c) Connect black wire to terminal L2 on generator set (9).
(d) Connect red wire to terminal L3 on generator set (9).
(e) Install generator set cover on terminal box.
c.
External Power Connection (208 Vac, 3-Phase, 4 Wire).
WARNING
To prevent injury to personnel and damage to the equipment, make sure generator set is
not operating when connecting or disconnecting power cable. Refer to TM 5-6115-58-
12/34 for generator set shutdown instructions.
(1) Shutdown refrigeration unit (TM 9-4110-252-14).
4-6