TM 10-3930-675-20-10043 00-6TOPHANDLER TILT TROUBLESHOOTING - CONTINUED0043 00Table 4. Error Code 261 - Tophandler Tilt OUT Control, Wiring Circuit FailureTroubleshooting Procedures - Continued.MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONError Code 261 - Tophandler Tilt OUT Control,Wiring Circuit Failureb. If voltage is not present,enter “DIAG ATTACH-MENT 13 (16)” menu andcheck current of TILT OUTOUTPUT. Current shouldbe present with joystickactivated to tilt tophandlerout.a. If current is not present,replace ECU (791) (WP 007600).b. If current is present, notifySRA.Table 5. Error Code 262 - Tophandler Tilt OUT Control, Component Failure Troubleshooting Procedures.MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONError Code 262 - Tophandler Tilt OUT Control,Component Failure1. Check wires and cables fromtophandler control valve toboom for obvious damage.Repair or replace damagedconnectors (WP 0111 00).2. Disconnect electricalconnector 6010 fromtophandler tilt OUT solenoid.Place ignition switch to ONposition. Error code 261 willbe displayed. Perform voltagecheck.If 20-25V is present at connector6010, replace tilt OUT solenoid(WP 0169 00).3. Disconnect connector X188from tophandler junction boxat end of boom. Place ignitionswitch to OFF position andcheck continuity betweenconnector 6010 pin 1 and pin2 and between connector6010 pin 1 and pin 2 andchassis.a. If continuity is not present,repair or replace connectors(WP 0111 00). b. If wiring harness requiresreplacement, notify DSMaintenance.DIAG TOP LIFT 13(16)OUTPUT/INPUTTILT IN 0mA0mATILT OUT 0mA0mA