Table 3-1. Operator Troubleshooting Instructions - Continued
4.
TEMPERATURE INSIDE CONTAINER WILL NOT STABILIZE.
Step 1. Check for improperly stacked cargo inside container.
Restack cargo as required so that:
a. Cargo does not block refrigeration unit evaporator coil (on container front wall).
b. Cargo is stacked no higher than one foot from container ceiling.
c. Air can circulate between cargo and container side walls.
Step 2. Check for open or unlatched rear doors.
Close and latch doors.
Step 3. Check for loose escape door.
Open rear doors.
Tighten escape door handles.
Step 4. Inspect rear doors for damaged or missing seals.
If doors are damaged or defective, notify unit maintenance.
Step 5. Check operation of refrigeration unit (TM 9-4110-258-13).
Troubleshoot refrigeration unit malfunctions in accordance with TM 9-4110-258-13.
Step 6. Check generator set for proper power output (TM 5-6115-585-12/34).
Troubleshoot generator set malfunctions in accordance with TM 5-6115-585-12/34.
5.
GENERATOR SET NOT OPERATING PROPERLY.
Troubleshoot generator set malfunctions in accordance with TM 5-6115-585-12/34.
Section III. OPERATOR MAINTENANCE PROCEDURES
a. There are no operator maintenance task requirements on the refrigerated container.
b. Refer to TM 9-4110-258-13 for operator maintenance procedures applicable to the refrigeration unit.
c. Refer to TM 5-6115-585-12/34 for operator maintenance procedures applicable to the generator set.
3-3/(3-4 Blank)