TM 55-8145-202-14
b.
Installation.
(1) Connect 5 foot (1.5 m) power cable (1) to refrigeration unit cable (2).
(2) Check that interior light cable is connected to 110 VAC junction box in the refrigeration unit.
CAUTION
To prevent damage to refrigeration unit, stop operation immediately if fan motor runs backwards.
(3) Service, start, and operate generator set (TM 5-6115-585-12/34).
(4) Service, start, and operate refrigeration unit (TM 9-4110-258-13).
(5)
Check rotation of fan motor on refrigeration unit (TM 9-4110-258-13). If motor runs backwards,
shutdown refrigeration unit (TM 9-4110-258-13) and generator set (TM 5-6115-585-12/34). Refer to
refrigeration unit (TM 9-4110-258-14) and reverse input power leads.